VL-TR-08 Time Relay

  • Instantaneous power-on, delayed power-off — no auxiliary power supply needed
  • Operates from an internal energy-storage capacitor after power loss
  • Rotary (0.1–10 minutes) or digital display (0.1–999 seconds) delay setting
  • High mechanical life: 5×10⁶ operations
  • Compact 18mm width, standard 35mm DIN rail installation
SKU: VL-TR-08 Category:
Request a Quote

VL-TR-RT8(S)-D — Capacitor-Powered Instant-On / Delay-Off Relay

This time delay relay provides instantaneous power-on and delayed power-off control, allowing reliable operation in systems where control signals must be delayed after shutdown. It is ideal for emergency lighting, instrumentation control, motor startup, and other similar applications.

The relay supports a wide working voltage range (AC/DC 24–240V) and operates without an auxiliary power supply, relying on an internal energy storage capacitor to function after power-off. Adjustable delay options include rotary type (0.1–10 minutes) and digital display type (0.1–999 seconds). Its compact 18mm width design supports standard 35mm DIN rail installation, making it easy to integrate into control panels and distribution cabinets.

Key Features

  • Instantaneous power-on, delayed power-off — no auxiliary power supply needed
  • Operates from an internal energy-storage capacitor after power loss
  • Rotary (0.1–10 minutes) or digital display (0.1–999 seconds) delay setting
  • High mechanical life: 5×10⁶ operations
  • Compact 18mm width, standard 35mm DIN rail installation

Technical Specifications

Parameter Rotary (D) Digital (S-D)
Working voltage AC/DC 24–240V ±10% AC/DC 24–240V ±10%
Power-off delay range 0.1s–10min, 4 gears 0.1s–999s
Delay accuracy Basic <0.5%, mechanical <10% Basic <0.5%
Minimum power-on time > 2s
Reset time < 300ms
Output configuration 1×SPDT, 16A (AC1-resistive)
Electrical durability 5×10⁶ (resistive load, 1s on / 9s off)
Environment Working -10 to 55°C, ≤85% RH, ≤2000m altitude · Storage -20 to 75°C, no rain/snow/salt fog/corrosive gas

Applications

Emergency lighting, instrumentation control and motor startup applications where the control signal must remain live for a set period after shutdown.

Downloads

Technical documentation for this product (datasheet, type-test report, CAD drawing) is being finalized and will be published here shortly. Need it sooner? Contact us via the Request a Quote form and our team will send it directly.

Packaging & Logistics

Packaging details, minimum order quantity, lead time and HS code for this product are being finalized and will be published here shortly. Need this information sooner? Contact us via the Request a Quote form.

Key Specifications

AC/DC 24-240V, capacitor-powered